By installing the VA-EOL end of line supervision board, the system can adapt the changing impedance when adjusting multiple VAT volume attenuators without loopback cable, and use time-sharing which approaches to detect open or short circuit for each branch. The system can indicate which speaker line is open/short circuit within 90 seconds (EN54-16 requirement), helping to save the analysis time.
- Monitor the status of the loudspeaker line and all of its branches without additional loopback cabling.
- Detect if there's speaker line short circuits or open circuits faults by monitoring the terminated resistance value.
- Compatible with 100V and 70V loudspeaker lines.
- The VA-EOL is mounted inside the case of the last loudspeaker on the loudspeaker line.
Electrical
- Power source: Supplied from BTQ-VM/SG/SL
- Max power consumption: 0.8W
- Speaker line: Applicable to 70V or 100V speaker line
Mechanical
- Dimensions (W x H x D): 80mm x 10mm x 60mm
- Weight: 0.10 kg