DIVA Matrix

More information »

Main Controller

DIVA-8MG2

  • - Public Address and Voice Alarm system control unit
  • - Designed for small to medium installations
  • - 8 zones
  • - 2 channels audio distribution for paging and BGM
  • - Up to 1000 W wattage capacity per amplifier channel
  • - Up to 128 zones (one controller and 15 secondary units)
  • - Loudspeaker line surveillance for A/B zone wiring
  • - EN54-16 certification
  • Main Controller (0)
  • Main Controller (1)
  • Main Controller (2)
  • Main Controller (3)
DIVA is a compact PA/VA system specifically designed for small to medium scale installations. It has all the essential functionality to comply with EN54-16 requirements for Voice Alarm, including full system monitoring, loudspeaker line impedance surveillance, microphone surveillance and monitored interfacing with remote devices.

DIVA-8MG2 is a 2 channel PA/VA controller with a maximum of 128 zones. It provides enhanced digital audio processing (DSP), a digital message player with up to 45 minutes message storage, a fully monitored fireman microphone, amplifier monitoring with switchover to backups and loudspeaker line monitoring for 16 audio lines (8 lines A/B).

For larger installations, up to 15 DIVA-8S slave units can be added to the system. The master unit amplifiers can share their power with slaves units, where more power is needed.

  • Small to medium scale installation
  • EN54-16 certified
  • Powerful Digital Signal Processing (DSP)
  • 8-zone system controller with individual volume controls per channel
  • Simultaneous announcement up to 128 zones
  • 2" full colour TFT screen
  • 5 audio inputs (2 x line, 1 x MIC/line, 1 x PSS or PSM,1 x Fireman Mic
  • 2 channel audio distribution for Paging and BGM
  • 1000 Watts maximum load/100V line outputs per channel amplifier
  • Enhanced loudspeaker line surveillance for A/B zoned installations
  • 9 monitored logic control inputs, 8 non-monitored logic control inputs, 8 Logic relay contacts, 1 Fault & 1 Evac relays outputs
  • Ethernet interface for configuration, control, diagnostics and logging
  • Digital storage for up to 45 minutes of pre-recorded messaging
  • Modbus, notifier, Vox@Net, TERRACOM interface
  • Full monitoring of PSS and PSM paging consoles
  • Combined back-up amplifier function
  • 1 Fault relays & 1 EVAC relays outputs
  • Programmable of 21 priority levels

Electrical

  • Mains power supply
    • Voltage: 230 / 115 VAC ±15%, 50 / 60 Hz
    • Power consumption: 48 W
  • Battery power supply
    • Voltage: 18 - 30 VDC

Audio 

  • Audio Line inputs 
    • Connector: 2 x 2 RCA (un-balanced)
    • Frequency response: -3 dB @ 20 Hz and 20k Hz
    • SNR: > 76 dB (Line-level) / > 78 dB (Mic-level)
    • THD: < 0.02% @ 1k Hz
    • Input sensitivity: 770 mV (0 dBu ~ -60 dBU)
    • Input impedance: 10 k Ohms
  • Fireman microphone
    • Connector: 5-pin locking-DIN
    • Frequency response: -3 dB @ 20 Hz and 20k Hz
    • SNR: > 70 dBu
    • THD: < 1% @ 1k Hz @ 8 Ohms
    • Signal: -40 to -30 dBu
    • Output impedance: 10 k Ohms
  • Monitor loudspeaker
    • Frequency response: -3 dB @ 200 Hz and 20k Hz
    • SNR: > 70 dB
    • THD: < 5% @ 1k Hz @ 8 Ohms
    • Signal: 16 dBu
  • Amplifier capacity (per channel): 1000 W

Environmental

  • Operating temperature: -5°C ~ 55°C (23°F ~ 131°F)
  • Storage temperature: -40°C ~ 70°C (-40°F ~ 158°F)
  • Relative humidity: 20% to 95%
  • Air pressure: 600 to 1100 h Pa
  • Heat dissipation: 140 BTU:hr

Mechanical

  • Dimensions (HxWxD): 88 x 483 x 338 mm 
  • Weight: 7.5 Kg 
  • Mounting: 19" 2U rack
  • Colour: RAL7016


Type File Name Download
Catalogue
[PDF] PAVA_Catalogue
Brochure
[PDF] DIVA System_Brochure
Datasheet
[PDF] DIVA-8MG2_Datasheet
Type File Name Download
Catalogue
[PDF] PAVA_Catalogue
Fiche produit
[PDF] DIVA-8MG2_Fiche produit
Type File Name Download
Datenblatt
[PDF] DIVA-8M_Datenblatt
Ausschreibungstexte
[DOCX] A&I Spezifikation DIVA-8MG2_docx
[PDF] A&I Spezifikation DIVA-8MG2_pdf