PRIMA VA Matrix

More information »

Digital Controller with 6 Integrated Class-D Amplifiers - 800W

PRIMA-VA/680R

  • - Compact PA/VA controller
  • - 6 monitored Class-D amplifiers
  • - 250 Watts per output
  • - 800 Watts all outputs combined
  • - 6 zones or 5 zones with back-up amplifier
  • - Permanent line monitoring
  • - IP connectivity
  • - EN54-16 certification
  • Digital Controller with 6 Integrated Class-D Amplifiers - 800W (0)

PRIMA-VA/680R is a compact PA/VA controller that offers 6 loudspeaker outputs. It is integrated with 6 high efficiency Class-D amplifiers built-in and is capable of handling loudspeaker output power of 250 Watts per zone which provides ease of system wiring and installation. One amplifier can also be used as a back-up amplifier.

PRIMA-VA/680R is based matrix control functions and digital message players, with front access for a fully monitored fireman microphone and an emergency message trigger button. The controller integrates our latest technology "Flexcontrol" providing you a huge potential for system configuration. Different types of settings can be freely assigned to the 6 potentiometers located in front go the unit.

The controller has 8 monitored logic control inputs, 8 relay outputs, 2 interfaces for paging consoles (PSS-G2, CD8-G2 or PSM8WJB), 2 balanced audio inputs which allow to connect audio sources such as music sources and HF microphone, 1 audio output for Third Party Control, 1 Ethernet port and 6 independent amplifier outputs. A XLR 5 pin connector is available on front panel for the optional monitored fireman microphone PRIMA-VA/FM.

Thanks to it's IP connectivity, PRIMA-VA/680R enjoys extreme flexibility. The system is SIP compatible and can communicate with the entire range of Audio over IP Vox@ products, as well as the Vox@net g2 audio server software, allowing interconnections with remote sources and endpoints.

Up to 256 PRIMA VA systems can be connected to each other. From a single solution to an IP networked application, PRIMA VA system easily adapts to a wide range of your applications.

PRIMA-VA/680R can be easily set up thanks to it's web browser, for both "Basic" and "Advanced" configurations. Several parameters, such as volume control, priorities, source selection, etc. can be configured from the web server.

As a Voice Evacuation System, PRIMA VA is certified to the EN54 standard. All its components and peripherals are constantly monitored, and all incidents (faults and alarms) are recorded in a history file that can be read via Webb browser.

  • 6 monitored Class-D amplifiers
  • 250 Watts per output
  • 800 Watts all outputs combined
  • Up to 6 loudspeaker zones or up to 5 loudspeaker zones with 1 back-up amplifier or up to 3 A/B loudspeaker zones
  • Simultaneous routing of 6 different audio sources on the 6 zones
  • Permanent line monitoring
  • Free assignment of settings on the 6 potentiometers
  • Up to 4 simultaneous IP audio streams 
  • Up to 4 message players
  • Message storage (more than 1 hour capacity in mp3)
  • IP connectivity: compatible with Vox@ range and Vox@net g2
  • Easy integration with IPBX via SIP protocol
  • Up to 256 PRIMA VA Systems can be connected together
  • SNMP protocol for remote monitoring
  • Audio output for Third Party Control

Electrical

  • AC power input: 115 VAC ~ 230 VAC, 50/60 Hz
  • Maximum output power: 800 W burst
  • Maximum consumption: 1.7 A by 230 VAC

Backup power supply

  • Voltage range: 21.6 to 28.8 VDC
  • Maximum consumption: 12 A by 28 VDC

Audio Characteristics

  • Audio inputs: 2
  • Bandwith: 20 Hz - 20k Hz
  • SNR: 87 dB 
  • THD: < 0.2% 

Loudspeaker Lines

  • Number of loudspeaker lines: 6
  • One output: 250 W burst
  • All outputs combined (100 V mode): 800 W (all channels combined)
  • Bandwith: 20 Hz - 20k Hz
  • SNR: 87 dB 
  • THD: < 0.2%

Mechanical

  • Dimensions (W x H x D): 482 x 88 x 432 mm
  • Weight: 8 kg
  • Mounting: 19'' 2U rack
  • Colour: RAL7016

Environmental

  • Operating temperature: -10°C ~ +50°C
  • Storage temperature:  -20°C ~ +60°C
  • Relative humidity: < 93%
  • Schools
  • Stores
  • Shopping malls
  • Hotels
  • Train stations
  • Universities
  • Industrial sites
Type File Name Download
Brochure
[PDF] PRIMA VA System_Brochure
Datasheet
[PDF] PRIMA-VA/680R_Datasheet
Type File Name Download
Brochure
[PDF] Système PRIMA VA_Brochure
Fiche produit
[PDF] PRIMA-VA/680R_Fiche produit
Type File Name Download
Broschüre
[PDF] PRIMA VA System_Broschüre
Datenblatt
[PDF] PRIMA-VA/680R_Datenblatt
Type File Name Download
Brošure
[PDF] PRIMA VA_Brochure
Tabele sa podacima
[PDF] PRIMA-VA/680R_Datasheet
Type File Name Download
Folleto
[PDF] PRIMA VA_Folleto
[PDF] PRIMA VA_Folleto
Ficha técnica
[PDF] PRIMA-VA/680R_Ficha tecnica

Related products