The CD8-G2 / CD16-G2 paging consoles are remote paging interfaces with access level 2 protection in compliance with EN54-16. These consoles are compatible with DIVA systems.
It serves up to 8/16 individual zones with an all-call button. Zone selection buttons and fireman microphone are encased in a heavy-duty IP30 wall-mount metal box with a lockable door.
The CD8-G2 / CD16-G2 zone buttons can represent a single zone or group of zones and are easily programmed through the system GUI using "drag and drop" functionality. The Push-To-Talk button can be programmed for PTT or latching operation. System status indicators show the status of all zones and indicators are also provided for Power, Evac and Fault.
The CD8-G2 / CD16-G2 is powered over RS485 via CAT5 (FTP/STP), however if power is not available over RS485 it can be locally powered using a 24 VDC supply.
- Wall-mount heavy duty remote paging console with Access level 2 protection to comply with the EN54-16
- 8 / 16 zone selection buttons
- All-call button
- LED test button
- Power indicator
- EVAC indicator
- Status and Fault indicator
- Compatible with DIVA8 System and communicate over a dedicated RS485 for Power, Audio and Data
- 1 unit is secured on Controller or Slave unit. 2nd and more on Controller or Slave are note secured.
- Max. 32 unit in a system and 10 in Controller-Slave string
- EN54-16 certified
Electrical
- Power supply: RS485 (RJ45/CAT-5)
- DC / battery power requirements:
- Voltage: 18 - 26 VDC
- Power consumption: 120 mA (CD8-G2) / 150 mA (CD16-G2)
Audio
- Frequency response: -3 dB @ 200 to 8k Hz
- THD: < 1% @ 1k Hz
- Output level Max: 6 dBu
- Noise gate threshold: -84 dBu - 24 dBu
- Attack time: 8 ms
- Release time: 100 ms
- Monitoring speaker:
- Impedance: 4 Ohms
- Output power: 1 W @ 1k Hz
- Frequency response: -3 dB @ 200 to 12k Hz
- System connection:
- Cable type: CAT-5
- Length: 100 m
Environmental
- Operating temperature: -5 ºC ~ +55 ºC
- Storage temperature: -40 ºC ~ +70 ºC
- Relative humidity: 15% to 90%
- Air pressure: 600 to 1100 h Pa
- IP rating: 30
- Heat Dissipation:
- CD-8G2: 10 BTU/hr
- CD-16G2: 12 BTU/hr
Mechanical
- Dimensions (W x H x D)
- CD8-G2: 318.6 x 187 x 130 mm
- CD16-G2: 348.6 x 247 x 130 mm
- Weight
- CD8-G2: 3.6 Kg
- CD16-G2: 4.7 Kg
Type |
File Name |
Download |
Catalogue |
[PDF] |
PAVA_Catalogue |
|
Brochure |
[PDF] |
DIVA System_Brochure |
|
Datasheet |
[PDF] |
CD-8G2_Datasheet |
|
[PDF] |
CD-16G2_Datasheet |
|
Type |
File Name |
Download |
Catalogue |
[PDF] |
PAVA_Catalogue |
|
Type |
File Name |
Download |
Datenblatt |
[PDF] |
CD-8G2_Datenblatt |
|
[PDF] |
CD-16G2_Datenblatt |
|
Ausschreibungstexte |
[DOCX] |
A&I Spezifikation CD-8G2_docx |
|
[PDF] |
A&I Spezifikation CD-8G2_pdf |
|
[DOCX] |
A&I Spezifikation CD-16G2_docx |
|
[PDF] |
A&I Spezifikation CD-16G2_pdf |
|