Security PAVA Power Amplifiers The SPA amplifiers are primarily designed for integration into Voice Alarm systems, but thanks to its flexibility, it can also be used for any Public Address or Commercial application. SPA amplifiers are certified to the EN 54-16 standard.
SPA Series

The SPA amplifiers are 2U high 19” rack mountable, 2-channel power amplifiers. Transformer isolated for 100 V, 70 V and 8 Ohm low-impedance distributed loudspeaker systems.

There SPA amplifiers range comprises three models:

  • SPA2060: 2 x 60 Watt
  • SPA2120: 2 x 120 Watt - Compliant to EN54-16 standard
  • SPA2240: 2 x 240 Watt - Compliant to EN54-16 standard

The SPA can be powered by either a 220 VAC mains supply or 24 VDC supply able to support a battery back-up system for use in the event of mains failure and emergency evacuation systems.

SPA amplifiers have short-to-ground, short-circuit, overload and temperature overheat protection including line-impedance surveillance with a maximum of 5% deviation using the DIVA8 or IDA8 systems for loudspeaker-line surveillance. They support both single spur and redundant loop (A/B) cabling.

  • SPA2060: 2x 60 Watt
  • SPA2120: 2 x 120 Watt - Compliant to EN54-16 standard
  • SPA2240: 2 x 240 Watt - Compliant to EN54-16 standard
  • 2 U high, 19'' rack mountable
  • Front panel indicators include : AC or DC power supply, Line overload and Temperature overload



Mains power supply

  • Voltage 230 VAC +/- 10%, 50/60 Hz
  • Power consumption** standby - idle* - Pmax
  • SPA2120: 28 W - 150 W - 322 W
  • SPA2240: 64 W - 287 W - 655 W
  • ** (Total Mains-power consumption)
  • * Idle: Measured with 10 Volt surveillance tone on the output

Battery power supply

  • Voltage: 21-28 VDC
  • Power consumption*** standby - idle* - Pmax
  • SPA2120: 0.25 A - 2.9 A - 6.4 A
  • SPA2240: 0.30 A - 5.47 A - 12.3 A
  • *** (Per ch. @ 28 VDC)
  • * (Alarm cycle + 10 V pilot-tone @ 28 VDC)
  • Line inputs: 2 (one per channel)
  • Connector: 3-pin XLR and 3-pin Phoenix

  • Frequency response: +/- 3 dB @ 40 Hz and 20 kHz
  • S/N: > 90 dB
  • THD: < 1% @ 1 kHz
  • Input range: -6 dBV to 6 dBV / 770 mV
  • Input impedance: 22 kΩ

Loudspeakers outputs

SPA2120

  • Rated load resistance: 100 Ohms (100 V) - 50 Ohms (70 V)
  • Rated load capacitance: 60 nF (100 V) - 125 nF (70 V)
  • Rated output power (per channel): 120 W (cont at 40° C)
  • Frequency response: 40 Hz to 20 kHz (-3 dB)
  • S/N: >  90 dB (no pilot tone)
  • Crosstalk: < 80 dB at nominal load for 1 kHz
  • Distortion: < 1% (@ 1 kHz) @ -10 dB of rated output power

SPA2240

  • Rated load resistance: 40 Ohms (100 V) - 20 Ohms (70 V)
  • Rated load capacitance: 125 nF (100 V) - 250 nF (70 V)
  • Rated output power (per channel): 240 W (cont at 40° C)
  • Frequency response: 40 Hz to 20 kHz (-3 dB)
  • S/N: >  90 dB (no pilot tone)
  • Crosstalk: < 80 dB at nominal load for 1 kHz
  • Distortion: < 1% (@ 1 kHz) @ -10 dB of rated output power

Mechanical

  • Dimensions (H x W x D) 19'' for table top use with feet: 92 x 440 x 305 mm
  • Dimensions (H x W x D) 19'' for rack use with brackets: 88 x 483 x 305 mm
  • Weight:
  • SPA2120: 12.3 Kg
  • SPA2240: 18.5 Kg
  • Mounting 19'' rack-mount
  • Color:  RAL7016

Environmental

  • Operating temperature: -5° C to +55° C
  • Storage temperature: -40° C to +70° C
  • Relative humidity: 15% to 90%
  • Air pressure: 600 to 1100 h PA
Type File Name Download
Catalog
[PDF] [en] PAVA_Catalog
[PDF] [fr] PAVA_Catalogue
Brochure
[PDF] [en] IDA8 System_Brochure
[PDF] [en] DIVA System_Brochure
Datasheet
[PDF] [en] SPA2120-SPA2240_Datasheet
[PDF] [fr] SPA2120-SPA2240_Fiche produit
[PDF] [fr] SPA2060_Fiche produit