IDA8 matrica

Više informacija »

Main Controller

IDA8C

  • - Public Address and Voice Alarm system control unit
  • - 8 zones 
  • - Up to 1000 W per zone
  • - Simultaneous control and routing of 48 audio channels over dedicated network
  • - Up to 256 zones via ATEÏS Local-Net
  • - Up to 8192 zones via ATEÏS Global-Net
  • - Loudspeaker line surveillance for A/B zone wiring
  • - EN 54-16 certification
  • Main Controller (0)
  • Main Controller (1)
  • Main Controller (2)
  • Main Controller (3)
  • Main Controller (4)

IDA8 is a highly integrated PA/VA system that complies with current architectural demands requiring IP and/or fiber-optic networking to allow for even the most complex of system designs.

The IDA8C is EN 54-16 certified for use on Public Address and Voice Alarm systems. All system components and peripherals are monitored. This monitoring extends from the capsule microphone to the end of a loudspeaker line. The external cables connected to the control inputs are monitored for short and open circuit and an internally generated pilot tone is available for monitoring impedance on the loudspeaker lines.

The IDA8C controller houses advanced audio digital processing (DSP), matrix control functions and a digital message player with front panel access for a fully monitored fireman's microphone and emergency trigger buttons. IDA8C also support amplifier monitoring with hot-swap amplifiers and loudspeaker line impedance monitoring.  

One IDA8C supports to connect to a maximum of 31 slave units via ATEÏS-Net. The slave units are available as single zone (IDA8S) or with A/B speaker line configurations (IDA8SAB), or for low-impedance monitoring (IDA8SL). The LCD touch screen panel on IDA8C gives the operators to see a detailed overview of the operational status of the entire system.


  •  Main Controller Unit for Public Address and Voice Alarm systems EN54 certified

Voice Alarm/Security

  • In accordance with EN54-16, ISO 7240-16 and BS5839/8-full monitored supervision from paging microphone capsule, amplifier monitoring to the end of loudspeaker line
  • Loudspeaker line surveillance for A/B zone wiring
  • Support redundant network cabling, wired as a redundant loop
  • Event logs and faults via LCD front panel or ATEÏS Studio software

Connectivity

  • Up to 48 simultaneous audio channels per local network
  • Up to 256 zones in a local network, and up to 8,192 zones in a global network
  • Full digital with 8 audio inputs & 8 audio outputs
  • 9 supervised control inputs & 8 control outputs, 1 fault & 1 EVAC relay outs
  • 2 dedicated & monitored device ports for paging consoles
  • Flexible used of network cards, CAT5-100 m & Fiber-20 Km
  • 32-bit DSP with superior A/D & D/A conversion
  • Internal digital message memory up to 100mins in WAV format (16k 16bit) or 400 mins in G.722 format

General

  • Front panel color touch-screen display, allowing navigation through various system menu’s
  • Cost-effective solutions using switching mode for multi-zoned amplifier
  • Message player and messages monitoring
  • Compatibility with the TERRACOM IP-media streamers
  • Alarm and chime-tones are stored in the IDA8C and IDA8S(AB) units
  • Full system redundancy using the IDA8RU switching devices

 

 Electrical

  • Mains power supply
    • Voltage: 115/230 VAC ±15%, 50/60 Hz
    • Power consumption: 48 W
  • Battery power supply
    • Voltage: 18 - 30 VDC

Audio 

  • Frequency response: ±1 dB @ 20 Hz and 20k Hz
  • Line inputs (Optional audio input card)
    • Connector: 3-pin phoenix
    • Frequency response: ±1 dB @ 20 Hz and 20k Hz
    • SNR: >81 dBA
    • THD: < 0.02% @ 1k Hz
    • Input sensitivity: 0~66 dBu / 6 dB steps
    • Input impedance: 10k Ohms
  • Line outputs (Optional audio output card)
    • Connector: 3-pin phoenix
    • SNR: >81 dBA
    • THD: < 0.02% @ 1k Hz
    • Signal: 0 dB
    • Output impedance: <100 Ohms
  • Amplifier capacity (per zone): 1000 W (max.)
  • Speaker line monitoring:
    • <5 Ohm (SHORT)
    • 5 ~ 5000 Ohm (Impedance value)
    • >5000 Ohm (OPEN)

Environmental

  • Operating temperature: -5°C ~ 55°C
  • Storage temperature:  -40°C ~ 70°C
  • Relative humidity: 20% to 95%
  • Air pressure: 600 to 1100 hPa

Mechanical

  • Dimensions (H x W x D): 88 x 486 x 313 mm
  • Weight: 5.40 Kg 
  • Mounting: 19"- 2U rack mount


 

Overview diagram IDA8C
Tip Naziv Preuzimanje
Catalogue
[PDF] PAVA_Catalogue
Brochure
[PDF] IDA8 System_Brochure
Datasheet
[PDF] IDA8C_Datasheet
Commercial Presentation
[PDF] IDA8 System_Presentation
Tip Naziv Preuzimanje
Brochure
[PDF] IDA8_Brochure
Catalogue
[PDF] PAVA_Catalogue
Fiche produit
[PDF] IDA8C_Fiche produit
Présentation Commerciale
[PDF] Système IDA8_Présentation
Tip Naziv Preuzimanje
Datenblatt
[PDF] IDA8C_Datenblatt

Slični proizvodi